Specifications of Petrol pumps/Gas stations Click
RATING 6KVA 10KVA
INPUT AC RANGE Undervoltage 140 +/- 5 V
Undervoltage Restoration 145 +/- 5 V
Overvoltage 260 +/- 5 V
Overvoltage Restoration 255 +/- 5 V
OUTPUT ON INVERTER MODE Maximum Power 6KVA 10KVA
Maximum Watts 4750W 7900W
Maximum Efficency 79% 78%
Voltage (INVERTER Mode) 220 V Nominal +/- 9%
Voltage (Mains Mode) Same as Input
Frequency (INVERTER Mode) 50 Hz. +/- 2%
Frequency (Mains Mode) Same as Input (45-55 Hz.)
Overload > 110 %
Transfer Time (typical a.s) 45 ms.
INVERTER MODE PROTECTION Low battery protection ElectronicTrip
Battery reverse protection Through fuse
Inverter mode over load ElectronicTrip
Inverter mode short circuit ElectronicTrip
MAINS MODE PROTECTION Over load / Short circuit Through MCB
Charger protection Through MCB
BATTERY Type 120 AH- 150AH Lead Acid Type
Number 10 15
Typical Recharge Time 10-12 Hrs.
BATTERY CHARGER Constant Voltage with current limit type 10Amp with boost voltage 138V and float voltage 135V 207V/ 200V
TECHNOLOGY High power factor boost charger
LED DISPLAY Switch On 16 x 2 CHARACTER USER FRINDLY DISPLAY WITH BACK LIGHT
INVERTER ON
Low Batery Pre-Alarm
Battery Low
Mains On
Smart Charge
Overload
Short Circuit
Battery fuse fail
Battery reverse
MCB Trip
ALARMS Low Battery Pre-Alarm Continuous Beeping
Overload Pre alarm Continuous Beeping
Short Circuit Continuous Beeping
MCB Trip Continuous Beeping
ENVIRONMENTAL Operating Temperature 0-40o C
Storage Temperature 0-40o C
Humidity 0-95 % RH non -condensing
    * Due to Continuous Product improvements,specs are subject to change without notice.