| RATING |
6KVA |
10KVA |
| INPUT AC RANGE |
Undervoltage |
140 +/- 5 V |
| Undervoltage Restoration |
145 +/- 5 V |
| Overvoltage |
260 +/- 5 V |
| Overvoltage Restoration |
255 +/- 5 V |
| OUTPUT ON INVERTER MODE |
Maximum Power |
6KVA |
10KVA |
| Maximum Watts |
4750W |
7900W |
| Maximum Efficency |
79% |
78% |
| Voltage (INVERTER Mode) |
220 V Nominal +/- 9% |
| Voltage (Mains Mode) |
Same as Input |
| Frequency (INVERTER Mode) |
50 Hz. +/- 2% |
| Frequency (Mains Mode) |
Same as Input (45-55 Hz.) |
| Overload |
> 110 % |
| Transfer Time (typical a.s) |
45 ms. |
| INVERTER MODE PROTECTION |
Low battery protection |
ElectronicTrip |
| Battery reverse protection |
Through fuse |
| Inverter mode over load |
ElectronicTrip |
| Inverter mode short circuit |
ElectronicTrip |
| MAINS MODE PROTECTION |
Over load / Short circuit |
Through MCB |
| Charger protection |
Through MCB |
| BATTERY |
Type |
120 AH- 150AH Lead Acid Type |
| Number |
10 |
15 |
| Typical Recharge Time |
10-12 Hrs. |
| BATTERY CHARGER |
Constant Voltage with current limit type |
10Amp with boost voltage 138V and float voltage 135V |
207V/ 200V |
| TECHNOLOGY |
High power factor boost charger |
| LED DISPLAY |
Switch On |
16 x 2 CHARACTER USER FRINDLY DISPLAY WITH BACK LIGHT |
| INVERTER ON |
| Low Batery Pre-Alarm |
| Battery Low |
| Mains On |
| Smart Charge |
| Overload |
| Short Circuit |
| Battery fuse fail |
| Battery reverse |
| MCB Trip |
| ALARMS |
Low Battery Pre-Alarm |
Continuous Beeping |
| Overload Pre alarm |
Continuous Beeping |
| Short Circuit |
Continuous Beeping |
| MCB Trip |
Continuous Beeping |
| ENVIRONMENTAL |
Operating Temperature |
0-40o C |
| Storage Temperature |
0-40o C |
| Humidity |
0-95 % RH non -condensing |