| SPECIFICATIONS |
RATING |
600 VA |
800 VA |
1400 VA |
INPUT |
Regulated UPS Mode |
Undervoltage |
180 +/- 5 V |
Undervoltage Restoration |
185 +/- 5 V |
Overvoltage |
265 +/- 5 V |
Overvoltage Restoration |
260 +/- 5 V |
| Unregulated UPS mode |
Undervoltage |
100 +/- 10 V |
Undervoltage Restoration |
110 +/- 10 V |
Overvoltage |
300 +/- 10 V |
Overvoltage Restoration |
290 +/- 10 V |
| |
OUTPUT |
Maximum Power |
600 VA |
800 VA |
1400 VA |
| Voltage (UPS Mode) |
230 V Nominal |
| Voltage (Mains Mode) |
Same as Input |
| Frequency (UPS Mode) |
50 Hz. +/- 2% |
| Frequency (Mains Mode) |
Same as Input (45-55 Hz.) |
| Overload |
> 110 % |
| Transfer Time (typical a.s) |
10 ms. |
| |
BATTERY |
Type |
120 AH- 150AH Lead Acid Type |
| Number |
1 |
2 |
| Typical Recharge Time |
10-12 Hrs. |
| Protection |
LOW BATTERY,REVERSE POLARITY |
| |
LED DIsplay |
Switch On |
White |
| UPS ON |
Red |
| Low Batery Pre-Alarm |
UPS On & Low Battery Red |
| Battery Low |
Red |
| Mains On |
Red |
| Smart Charge |
Red ( Along with Mains On LED) |
| Overload |
Red Steady |
| Short Circuit under Battery Mode |
Overload RED LED Blinking |
| Short Circuit under Mains Mode |
Smart Charge ( Blinking ) |
| |
Alarms |
Low Battery Pre-Alarm |
Beeping every 10 seconds |
| Low Battery |
Continuous Beeping for 10 Seconds |
| Overload |
Continuous Beeping for 10 Seconds |
| No Load Shut Down |
Continuous Beeping for 10 Seconds |
| Short Circuit |
Continuous Beeping for 10 Seconds |
| |
Environmental |
Operating Temperature |
0-40 degree C |
| Storage Temperature |
0-40 degree C |
| Humidity |
0-95 % RH non -condensing |
| |
Due to Continuos Product improvements,specs are subject to change without notice. |
| |